Hot
R290 intarCUBE
R290 chillers
Chillers in compact construction with glycol, water or brine and a low charge of R290.
- Description
- TECHNICAL SPECIFICATIONS
- OPTIONAL AND ACCESSORIES
- Dimensions
- Documentation
Description
R290 intarCUBE chiller is a water or glycol chiller designed for commercial and industrial refrigeration applications, featuring a reduced R290 refrigerant charge.
CONSTRUCTION
- Self-supporting casing made of galvanised sheet steel with weather-resistant polyester coating, with thermo-acoustic insulation in elastomeric foam.
- Removable side panels around the entire perimeter.
- Independent compressor compartment separated from the condensing air flow.
- Sealed electrical panel, independent from the refrigerated compartment.
- Flow and return pressure gauges and thermometers.
FANS
- EC electronic fans with speed regulation by proportional control of the condensing pressure.
- Fans with independent air flow rates.
REFRIGERATION CIRCUIT
- Scroll or semi-hermetic compressors with capacity control, unloaded start and crankcase heater.
- Refrigeration circuit made of annealed copper tubing with brazed joints, filter drier, ATEX high and low pressure switches, pressure transducers and temperature probes.
- Stainless steel plate evaporator(s) brazed with pure copper and electronic expansion valve(s).
- Economiser by means of an internal heat exchanger.
HYDRAULIC CIRCUIT
- Hydraulic circuit made of copper tubing with threaded connections, with filling/drain valve, air vent, flow switch, and inlet and outlet thermometers and pressure gauges.
- Flow switch.
SECURITY
- ATEX fans for continuous ventilation of the refrigeration compartment.
- Leak detector with audible and visual alarm.
- Shunt trip coil for cutting off the power supply line to electrical components located in the refrigeration compartment.
- Safety valve on the high- and low-pressure sides for common ducted discharge.
COIL
- Copper microtube condenser coil with aluminium fins.
ELECTRICAL PANEL AND CONTROL
- IntarChiller electronic controller with refrigeration control, condensing fan control with floating setpoint, pump control, etc.
CONSTRUCTION
- Stainless steel screws.
- Silentblocks for unit installation. (Accessory)
FANS
- EC radial fans for air discharge to ambient.
REFRIGERATION CIRCUIT
- Heat recovery (20 or 80 % of condenser heat) for hot water production (only without integrated hydraulic module).
HYDRAULIC CIRCUIT
- Integrated hydraulic module with glycol circulating pump with stainless steel body and impeller, expansion vessel, safety valve, mesh filter, thermometers and pressure gauges, air vent and drain connection (except series 8 and units with heat recovery).
- Standby pump.
COIL
- Polyurethane-based anti-corrosion coating for the condenser coil.
- Aqua Aero® anti-corrosion coating for copper microtube finned coil.
- Anti-corrosion treatment on copper microtube and Alucoast® fin coil.